Recommended for increased asset lifetime with highly reliable performance and reduced operational risks.
KEY FEATURES
T401 gives state-of-the-art condition monitoring solution for industries with huge electrical infrastructure. It can analyze the data and obtain the predictive diagnostics to detect any serious faults before a breakdown occurs. T401 is precisely designed to monitor wide range of electrical asset types and to provide a greater visibility into the assets.
The T401 can acquire data and can easily integrate with existing third-party systems through serial communication like RS-485/ SFP (Gigabit Optical Ethernet). The T401 monitor comes with condition monitoring software (Rugged Connect/ RM EYE) which is designed to cater the needs of various commercial, industrial, and utility applications.
POWER SUPPLY | Input Power Requirement | 24/48 VDC ± 10% |
ANALOG/DIGITAL INPUT MODULE | Power Consumption | 20 Watts |
# of Input Channels | 08/04 Channels | |
Input Channel Types | Configurable from a range of input options, RTD, AC/DC current, AC/DC voltage, Potentiometer, Dry/Powered contact switch | |
| Accuracy of Channels | ±0.5% full scale input range |
ANALOG OUTPUT MODULE | # of Output Channels | 04 Channels |
| Output format | 4-20 mA or 0-5Vdc / 0-10Vdc (Configurable for any measured / calculated value) |
OUTPUT RELAY MODULE | # of Output Channels | 08 Form C relays (5A) |
| User Programmable | Yes, from Rugged Connect Software or webserver, if present |
DATA STORAGE & CONFIGURATION | Data Storage Capacity | 4 or 8 GB, Industrial Grade micro-SD, extendable to 2TB |
| Logging Rate | User Configurable, 1 sec interval on USB |
| System Fault Indication | 1 System Fault Relay, with Local LED light |
| Config port | USB (to use with Rugged connect windows software) |
COMMUNICATION | Serial Communication | 01 x RS-485 (RS-232 optional converter) |
| Ethernet Communication | 02 Ethernet Ports, configurable to RJ-45 or SFP (Gigabit Optical) |
| Redundancy | Support PRP Redundancy |
| Protocol Supported | Modbus, DNP3.0, IEC60870-104, IEC61850, Other protocols provided on request |
EMC TYPE TESTING | Conducted & Radiated Emissions | ICES-003 (2016), CISPR32 (2015), CISPR11 (2015) |
| ESD and EM Field Immunity | IEC61000-4-2, C37.90-3, IEC61000-4-3, C37.90.2 |
| Fast Transient & Surge Immunity | IEC61000-4-4, IEC61000-4-5, C37.90.2 |
| Magnetic Field Immunity | IEC61000-4-8, IEC61000-4-10 |
| Immunity from Conducted Disturbances | IEC61000-4-6, IEC61000-4-16 |
| Ripple, Dips & Damped Oscillatory | IEC61000-4-17, IEC61000-4-18, IEC61000-4-29 |
| Safety | IEC60255-26 and CE Certified |
ENVIRONMENTAL AND MECHANICAL | Operating Temperature | -40 to 72 °C |
| Operating Humidity | 95% Non Condensing |
| Storage Temperature | -40 to 85 °C |
| Dimensions | W26.7 cm x H7.2 cm x D18.7 cm (10.5’’ x 2.8” x 7.4”) |
| Weight | App. 1.5 to 2.0 Kg. (based on number of configuration) |