Ultra-High Frequency Partial Discharge Monitor for OEMs.
KEY FEATURES
Rugged Monitoring PD211 is a compact design, designed for reliable Partial Discharge (PD) Monitoring Module for Transformers, Switchgears, GIS and Power Cable Terminations.
PD211 is based on the UHF (Ultra High Frequency) technology for PD signal acquisition and analysis. The Monitor is a combination of reliability and user-friendly configuration software. It has two variants with 04 channel and 08 channels, that can connect to 4 and 8 UHF-PD sensors respectively. The system can be integrated with any UHF PD sensors that are having response between 100 MHz to 2000 MHz.
Number of Channels | | 04 or 08 (Simultaneous acquisition, No Multiplexing) |
Sampling Rate | | 125 Ms/s |
Acquisition Bandwidth | | 300Mhz - 2000Mhz |
Vertical Resolution | | 12-Bit |
PD Sensitivity | | -80dBm |
Noise Elimination | | |
- Band Pass Filters | | Tuneable for di erent frequencies including but not limited to 440Mhz, 800Mhz, 1100Mhz, and 1600Mhz |
- Software Noise Gating | | Advanced denoising algorithms |
Data Storage (Memory) | | MicroSD external memory slot (Up to 2 TB) |
Compatible PD Sensors | | Any Ultra High Frequency (UHF) PD Sensors with sensitivity 100Mhz - 2000MHz. |
Synchronization Inputs | | 2 Inputs (Internal and External) |
Serial Port | | RS-485 with Modbus RTU and Can Port with CANBUS protocol |
Configuration Port | | Ethernet Port for configuration |
Operating Temperature | | -30 to 75 °C |
Storage Temperature | | -40 to 85 °C |
Dimensions | | 4.92" x 4.92" x 1.89" (125mm x 125mm x 48mm) |
Humidity | | 95% Non Condensing |
Power Input | | 12 - 24V DC ( Default) |
Power Consumption | | 15W |
# of Relays Outputs | | 01 x Fail Safe Relay for System Failure |