Recommandé pour augmenter la durée de vie des actifs avec des performances très fiables et des risques opérationnels réduits.
CARACTÉRISTIQUES PRINCIPALES
T401 gives state-of-the-art condition monitoring solution for industries with huge electrical infrastructure. It can analyze the data and obtain the predictive diagnostics to detect any serious faults before a breakdown occurs. T401 is precisely designed to monitor wide range of electrical asset types and to provide a greater visibility into the assets.
The T401 can acquire data and can easily integrate with existing third-party systems through serial communication like RS-485/ SFP (Gigabit Optical Ethernet). The T401 monitor comes with condition monitoring software (Rugged Connect/ RM EYE) which is designed to cater the needs of various commercial, industrial, and utility applications.
SPÉCIFICATIONS TECHNIQUES
POWER SUPPLY
|
Input Power Requirement
|
24/48 VDC ± 10%
|
ANALOG/DIGITAL INPUT MODULE
|
Power Consumption
|
20 Watts
|
# of Input Channels
|
08/04 Channels
|
|
Input Channel Types
|
Configurable from a range of input options, RTD, AC/DC current, AC/DC voltage, Potentiometer, Dry/Powered contact switch
|
|
|
Accuracy of Channels
|
±0.5% full scale input range
|
ANALOG OUTPUT MODULE
|
# of Output Channels
|
04 Channels
|
|
Output format
|
4-20 mA or 0-5Vdc / 0-10Vdc (Configurable for any measured / calculated value)
|
OUTPUT RELAY MODULE
|
# of Output Channels
|
08 Form C relays (5A)
|
|
User Programmable
|
Yes, from Rugged Connect Software or webserver, if present
|
DATA STORAGE & CONFIGURATION
|
Data Storage Capacity
|
4 or 8 GB, Industrial Grade micro-SD, extendable to 2TB
|
|
Logging Rate
|
User Configurable, 1 sec interval on USB
|
|
System Fault Indication
|
1 System Fault Relay, with Local LED light
|
|
Config port
|
USB (to use with Rugged connect windows software)
|
COMMUNICATION
|
Serial Communication
|
01 x RS-485 (RS-232 optional converter)
|
|
Ethernet Communication
|
02 Ethernet Ports, configurable to RJ-45 or SFP (Gigabit Optical)
|
|
Redundancy
|
Support PRP Redundancy
|
|
Protocol Supported
|
Modbus, DNP3.0, IEC60870-104, IEC61850, Other protocols provided on request
|
EMC TYPE TESTING
|
Conducted & Radiated Emissions
|
ICES-003 (2016), CISPR32 (2015), CISPR11 (2015)
|
|
ESD and EM Field Immunity
|
IEC61000-4-2, C37.90-3, IEC61000-4-3, C37.90.2
|
|
Fast Transient & Surge Immunity
|
IEC61000-4-4, IEC61000-4-5, C37.90.2
|
|
Magnetic Field Immunity
|
IEC61000-4-8, IEC61000-4-10
|
|
Immunity from Conducted Disturbances
|
IEC61000-4-6, IEC61000-4-16
|
|
Ripple, Dips & Damped Oscillatory
|
IEC61000-4-17, IEC61000-4-18, IEC61000-4-29
|
|
Safety
|
IEC60255-26 and CE Certified
|
ENVIRONMENTAL AND MECHANICAL
|
Operating Temperature
|
-40 to 72 °C
|
|
Operating Humidity
|
95% Non Condensing
|
|
Storage Temperature
|
-40 to 85 °C
|
|
Dimensions
|
W26.7 cm x H7.2 cm x D18.7 cm (10.5’’ x 2.8” x 7.4”)
|
|
Weight
|
App. 1.5 to 2.0 Kg. (based on number of configuration)
|