GSENS2

Online Oil Analysis

Advanced Transformer Oil Monitoring Solution

GSENS2 precisely monitors fault gases, moisture, and oil temperature, enabling early detection and ensuring optimal transformer reliability.

Features
  • Rugged and Compact
  • Early Fault Detection
  • Optimized Maintenance Cycles
  • High and Repeatable Accuracy
  • Oil Extraction Connection
  • Mechanical Stability
  • Risk Mitigation
Benefits
  • Enhances transformer lifespan
  • Quick and easy installation.
  • Lower maintenance costs.
  • User-friendly interface for efficient monitoring
Applications
  • Transformers and oil-filled assets.
  • Instrument transformers.
  • Load tap changers.
  • Applicable to all classes of transformers
  • Compatible with new and retrofit installations.
Technical specifications

Technical Data

Degree of protection

IP 66

Dimensions

435 / 657 x 218 x 264 mm (version with short / long measuring pipe)

Device weight
  • Version with short measuring pipe: approx. 12 kg
  • Version with long measuring pipe: approx. 14 kg
  • (Without ball valve / flange / safety chain)
Ball valve weight

Approx. 6 kg (including flange and safety chain)

Interfaces

Relay Outputs
  • 4 freely configurable signaling relays (1 changeover contact each)
    for warning and alarm messages and for maintenance messages from
    the device-internal monitoring.
  • 1 signaling relay for safety messages (e.g., loss of voltage)
  • Contact current capacity:
    250 V AC / 5 A; max. 400 V AC, cos φ = 1 at 85 °C;
    30 V DC / 5 A to 300 V DC / 0.25 A
Analog outputs

Passive, signal tolerance 0.03 mA, load resistance max. 700 Ω at 24 V DC GSENSE DGA 200: 2 configurable outputs, 4…20 mA

Service interface

5-pole socket (Molex) for communication via Modbus RTU and parameterization
via MSET parameterization software

Electrical Connection

Voltage Supply

95…280 V AC, 50/60 Hz or 95…280 V DC (protected against polarity reversal)

Power Consumption

< 13 W

Over Voltage Category

III

Connection Terminals

 Voltage supply, relays and analog outputs: 2.5 mm2, AWG 14

Cable Gland

3 x M20 x 1.5 or 3 x .“ NPT; 8…15 mm lead diameter

Mechanical Testing
Vibration

10-150 Hz at 2 g, 2 h (IEC 60068-2-6)

Earthquake

2-10 Hz, 22.5 mm, 1 h (IEC 60068-2-57)

Shock

10 g, 10 ms (IEC 60068-2-27)

Parameterization Software
Delivery

On USB stick, included in the GSENSE2 scope of delivery

Operating system

Microsoft Windows 7 8 and up

Measured value display and evaluation

Display of the current measured values and device information.
Event database with time stamp (date and time); graphic display and evaluation
of the temporal progression of the measured values.
Export of the measured values (CSV file) or settings of a protocol (PDF file)

Parameterization

Configuration of the parameters for commissioning, communication, and ongoing operation

Adjustment
  • Setting the time stamp of the oil sample extraction.
  • Entry of the reference values in accordance with the laboratory report
Service

Reading out the internal device service database for further
analysis by RM experts

For detailed technical specifications, please refer to the brochures.

Our Presence Across the Globe

Head Office

CANADA
1415 Frank-Carrel, Suite
230, Quebec, QC – G1N
4N7, CANADA