Online Oil Analysis
Advanced Transformer Oil Monitoring Solution
GSENS2 precisely monitors fault gases, moisture, and oil temperature, enabling early detection and ensuring optimal transformer reliability.
Technical Data
IP 66
435 / 657 x 218 x 264 mm (version with short / long measuring pipe)
Approx. 6 kg (including flange and safety chain)
Interfaces
Passive, signal tolerance 0.03 mA, load resistance max. 700 Ω at 24 V DC GSENSE DGA 200: 2 configurable outputs, 4…20 mA
5-pole socket (Molex) for communication via Modbus RTU and parameterization
via MSET parameterization software
Electrical Connection
95…280 V AC, 50/60 Hz or 95…280 V DC (protected against polarity reversal)
< 13 W
III
Voltage supply, relays and analog outputs: 2.5 mm2, AWG 14
3 x M20 x 1.5 or 3 x .“ NPT; 8…15 mm lead diameter
10-150 Hz at 2 g, 2 h (IEC 60068-2-6)
2-10 Hz, 22.5 mm, 1 h (IEC 60068-2-57)
10 g, 10 ms (IEC 60068-2-27)
On USB stick, included in the GSENSE2 scope of delivery
Microsoft Windows 7 8 and up
Display of the current measured values and device information.
Event database with time stamp (date and time); graphic display and evaluation
of the temporal progression of the measured values.
Export of the measured values (CSV file) or settings of a protocol (PDF file)
Configuration of the parameters for commissioning, communication, and ongoing operation
Reading out the internal device service database for further
analysis by RM experts
For detailed technical specifications, please refer to the brochures.